How Do You Ground a New Bath Fan Without Old One Being Grounded

Old 12-22-04, 12:00 PM

Join Date: Aug 2002

Emplacemen: Orange County

Posts: 233

Received 0 Votes along 0 Posts

Grounding a Bathroom Fan


I plan to install a Nutone bathroom fan. The direction said this unit moldiness be grounded. My mansion was built in 1961 indeed it didn't come with a ground wire. Then am I at a short end now? What would a licensed physical phenomenon would recommend if I asked him to establis IT for me therein eccentric? Thx.

Old 12-22-04, 12:04 Promethium

Join Date: Sep 2003

Location: Central Unprecedented York State

Posts: 13,970

Received 0 Votes on 0 Posts

Run a newfound circle from the main panel.

Run a separate earthing telegraph from the independent panel.

Replace the wiring along the existing circuit from the main panel.

Old 12-22-04, 12:53 PM

Join Escort: Aug 2002

Location: Orange County

Posts: 233

Standard 0 Votes along 0 Posts

Thanks for your answer. The impanel is an old one with advertise-in breaker. I am not positive if it came with a ground

Old 12-22-04, 12:59 PM

Join Date: Feb 2002

Localization: port chester n y

Posts: 2,117

Received 0 Votes on 0 Posts

IF the cable for the connection is a cable with the conductors embedded in a metallic "armour", then the antimonial surface of the cable armor is the Groundind-conductor.You moldiness verify this by a voltage test-to-Ground, which is a emf-reading between the Illegal conductor and the cable armor.

Good Luck & Enjoy the Experience!!

Old 12-22-04, 02:43 PM

Join Date: Aug 2002

Fix: Orange tree County

Posts: 233

Received 0 Votes happening 0 Posts

You must verify this away a voltage examination-to-Ground, which is a voltage-recital between the Black conductor and the cable armor.

I don't remember if in that location is an armor. Will try later when I got nursing home. Should information technology read 120V?

Old 12-22-04, 07:24 PM

ampz's Avatar

Join Date: Feb 2004

Location: Philadelphia

Posts: 536

Received 0 Votes on 0 Posts

The NEC does non recognize the armor of certain types of armorcable {BX} as a realiable fault track.I urge pouring a unprecedented line from the panel.

Old 12-22-04, 09:00 Post meridiem

hornetd's Avatar

Join Escort: Aug 2001

Location: Maryland

Posts: 695

Received 0 Votes on 0 Posts

Is IT BX or character AC


If the spiral tape metalic armor has a bonding strip inside the armor to bond the spirals to to each one other then it is type AC cable. If there is nobelium bonding denudate then information technology is the older BX cable and the armour essential not be put-upon as an Equipment Grounding Conductor.
--
Turkey cock H

Old 12-23-04, 04:50 Postmortem

Get together Date: Aug 2002

Location: Orange County

Posts: 233

Received 0 Votes on 0 Posts

i chequered, just 2 wires. Mustiness rewire if I motive puritanical flat coat, I guess.